Using External Current Transformers with Other CR Devices

145

35 10

15

30

25

20

Many times, the application requirements do not allow using a single sensor such as a transducer or current sensing

relay. The level of the current sensed may be too great, the size of the conductor may be too large, or the location

of the sensor may not allow the placement of the transducer. In these cases, a two piece solution can be used, with

a remote or external transformer chosen for capacity, size, or location, and a transducer or current sensing relay for

input or control.

Typically, a standard 5 amp secondary current transformer is selected. These transformers integrate easily

with the 5 amp input transducers, transmitters and relays.

The accuracies listed under the burden values are given in percent. These values are for a full scale reading.

Percent accuracy means that the reading received from the transformer at the burden listed will be within the

percentage given of ideal. Hence, a 50 to 5 turns ratio transformer with 50 Amps through the window will

output 5 amps +/- 0.3% in the secondary into a 0.1 ohm burden. The current in the secondary will be

somewhere between 4.985 and 5.015 amps.

When the instrument connected gives the burden to the transformer in VA (volt-amps) the table can be used to

determine accuracy. Since the transformer has a 5 amp secondary, using Ohm’s Law, the impedance can be

determined. A burden of 5 VA must be equal to the current squared times the impedance in ohms. Thus, 5VA /

(5X5) = 0.2 Ohms. The accuracy of this transformer-meter system would be 0.6%.

If the impedance calculated or chosen falls between headings, use interpolation to determine accuracy.

In general, the lower the burden, the higher the accuracy.

It is critical to understand that the accuracy ratings are for a full scale reading. This accuracy will only be

maintained from 10% full scale and up. Below this, and the accuracy worsens greatly. Always strive to select

transformers so that the majority of readings will be within the 10 to 100% full scale range.