Precision, AC Current to Voltage Transducer
The CR4310 series
current-to-voltage transducer produces a 0-5 Vdc output signal that is directly
proportional to the input AC current. The output signal is average-sensing, calibrated for
RMS.
This transducer is used with process control and industrial instrumentation equipment.
The DC output signal can be connected directly to a high impedance analog input of a
computer or PLC without additional signal conditioning.
The CR4310 series will measure up to 200% of full scale on a short time basis (1 minute
or less) and 150% on a continuous basis at its rated accuracy.
To protect external circuits from damage caused by short circuits or motor inrush
currents, the output is limited to 12 Vdc.
Features
|
|
- Output overload protected
|
|
|
|
|
- Self-powered, requires no external power source
|
Specifications
| Accuracy: Depends on the range and load resistance, see Part Numbers table |
| Ripple: 1% Max. peak ripple on output |
| Calibrated Signal Out: 0-5 Vdc |
| Response Time: 250 ms max., 10-90% FS |
| Max. Signal Out: 12 Vdc |
| Frequency: 50/60 Hz |
| Insulation Class: 600 V, BIL 10 kV Full Wave |
| Operating Temperature Range: -30° to +60° |
| Load Resistance: See part numbers table for minimum resistance that will
provide rated accuracy. Higher resistance will provide improved accuracy. |
Part Numbers
| CR4310-* CURRENT TO VOLTAGE TRANSDUCER |
| * |
Range in AC Amps |
Accuracy
% FS |
Minimum Load Resistance in OHMS |
| 5 |
0-5 |
1.0 |
1MEG |
| 10 |
0-10 |
0.75 |
800K |
| 15 |
0-15 |
0.75 |
800K |
| 20 |
0-20 |
0.5 |
400K |
| 30 |
0-30 |
0.5 |
400K |
| 50 |
0-50 |
0.5 |
160K |
| 75 |
0-75 |
0.5 |
160K |
| 100 |
0-100 |
0.5 |
80K |
| 150 |
0-150 |
0.5 |
80K |
| 200 |
0-200 |
0.5 |
80K |
|