|
|
Application Guide
INSTRUMENT TRANSFORMER
APPLICATION GUIDE
INTRODUCTION
The primary purpose of this guide is to give the reader a basic understanding of how to
apply instrument transformers in a practical way while observing good engineering
practice. It is not intended to make the reader an instrument transformer designer. A
special effort will be made to keep to a minimum technical terms and language.
PURPOSE
The purpose of instrument transformers is to provide either a current or voltage at a
useable level to monitor the voltage or current in a given circuit. For example, it would
not be economical to have an ammeter to measure 600 amps in a conductor directly. It is
economical to have an ammeter to measure current over a range of 0 - 5 amps. By inserting
a current transformer in the circuit, it will produce a current which is precisely
proportionate to the current in the conductor you wish to monitor over a range of 0 - 5
amps which corresponds to 0 - 600 amps. The ammeter will have a scale of 0 - 600 amps.
Likewise, it would not be economical to measure a voltage of 14,400 volts directly. By
inserting a voltage transformer in the circuit a directly proportionate voltage over a
range of 0 - 120 volts will be present which corresponds to 0 - 14,400 volts. Current and
voltage transformers are also used to provide the energy to operate various protective
relays. The degree to which an instrument transformer produces a current or voltage that
is proportionate to the one to be monitored is referred to as its accuracy. This subject
will be covered in much greater detail later in this guide.
CURRENT TRANSFORMERS
As the name implies current transformers are generally used to step down current in a
very predictable fashion with respect to current and phase. For example, you wish to
measure the current being drawn by a motor to determine if the motor is lightly loaded or
being overloaded. First, you must know the voltage level of the motor circuit. From this
you can determine what voltage class insulation the current transformer should have. The
following is a list of the various voltage classes and some of the most common voltages
for each class:
| Voltage Class (KV) |
Voltage Range (KV) |
Common Voltages (V) |
| 0.6 |
0 - 0.6 |
120, 208, 240, 277, 380, 480, 600 |
| 1.2 |
0.601 - 1.2 |
840, 1200 |
| 2.5 |
1.201 - 2.5 |
2400 |
| 5.0 |
2.501 - 5.0 |
3300, 4200, 4800 |
| 8.7 |
5.001 - 8.7 |
6600, 7200 |
| 15.0 |
8.701 - 15.0 |
11000, 12000, 14400 |
| 25.0 |
15.001 - 25.0 |
18000, 24000 |
| 34.5 |
25.001 - 34.5 |
27600, 34500 |
The motor we wish to monitor is 480V, referring to the above would indicate a 0.6KV
(600V) voltage class. Next you should know the motor's Full Load Amps (F.L.A.). Our
motor's F.L.A. is 96 amps. A CT with a ratio of 100:5A would work, but you would be
pushing the upper limit of your meter if you had a meter with a 0-5A movement and a scale
of 0-100A. It would be better if you selected a CT with a ratio of 150:5A with a meter
movement of 0-5A and a scale of 0-150A. A CT with a 150:5A current ratio has a turns ratio
of 30:1 (150A/5A = 30/1). Therefore, if you have 96A in the primary, you should have 3.2A
in the secondary (96A/30 = 3.2A). This is perfect transformation which is not possible. In
any device there is always some degree of losses and distortion that takes place. These
losses and distortions will cause, in our example, the secondary to produce a current
somewhat different than 3.2A. Also there will be some difference in the wave form of the
secondary from the wave form of the primary. These differences are known as the accuracy,
or lack of, in the CT. The American National Standards Institute has published standards
which are generally accepted as guidelines for performance. In the case of instrument
transformers the applicable ANSI standard is C57.13. This publication serves as a
guideline for instrument transformers manufactured in the United States. According to ANSI
C57.13 there are two accuracy categories, metering and relay accuracies. For metering
there are 0.3, 0.6 and 1.2 which represent percent maximum ratio error when 100% of the
rated primary current is flowing. It is not a complete statement to say a current
transformer has a maximum ratio error of plus or minus 0.3%. It is only a complete
statement when an accuracy is stated at a given burden. ANSI C57.13 also defines burdens
with respect to OHMS and phase angle shift. Standard ANSI burdens are BO.1, BO.2, BO.5,
BO.9 and B1.8. These standard ANSI burdens are ohmic values of burden respectively, 0.1,
0.2, 0.5, 0.9 and 1.8 ohms of load.
You can convert the ohmic value of burdens to VA (volt-amps) by simply multiplying the
ohmic value by 25 for a current transformer with a 5 amp secondary. For example, the
standard ANSI burden of BO.2 is equal to 5 VA (0.2 X 25). Therefore, an ANSI statement of
metering accuracy such as 0.3BO.2 is saying that the current transformer's ratio error
shall not exceed 0.3% plus or minus at a burden not exceeding 0.2 ohms of burden. The ANSI
standard metering accuracy class also defines the maximum phase shift plus or minus as
well through the use of parallelograms which requires a technical background beyond the
scope of the intended reader.
ANSI relay accuracy class defines the performance of a current transformer under
certain conditions with respect to the burden the secondary of the current transformer
will support at a given voltage, as well as the maximum ratio error. All ANSI relay
accuracy classes require that the ratio error not exceed 10% plus or minus. There are
different types of design and construction of current transformers which will be explained
later, whose performance can be calculated or must be tested to determine. This is the
reason for the letter "C" or letter "T" prefix on the ANSI relay
accuracy classes. The standard ANSI relay accuracy classes are C10, C20, C50, C100, C200,
C400 and C800, or T10, T20, T50, T100, T200, T400 and T800. The numerical suffix is the
voltage that the current transformer's secondary must develop when the current in the
secondary is 20 times nominal. For example, if the nominal secondary current is 5A, the
designated voltage must be developed when the secondary current is 100A (20 X 5A = 100A).
Once again the accuracy is not a complete statement without a specified burden. In this
case the burden can be determined by dividing the numeric suffix by 100. For example C100,
100 divided by 100 equals a 1 OHM burden. In the case of a ANSI relay accuracy class of
C400 means that the maximum ratio error shall not exceed 10% plus or minus when 20 times
nominal current flows in the secondary and the secondary voltage will be 400V with a
burden of 4 OHMS. Also the letter "C" says that the design and construction is
such that the performance may be calculated.
TORROIDAL TYPE CURRENT TRANSFORMERS
In general there are three types of design and construction for current transformers.
They all have a magnetic core or cores and one or more windings. The most common type is
the torrodial or donut type which has no internal primary winding as such. The primary is
the conductor in which the current is to be monitored. The primary conductor is simply
placed through the window of the current transformer. The core in this type is a band of
magnetic grade steel concentricly wound upon itself. This is an extremely efficient core
design which has no breaks or gaps in the magnetic path. While other types of core designs
may produce relative high levels of audible noise, (approximately 30-70 DB's) the
torroidal core rarely produces an audible noise level. The torroidal or donut type current
transformer is very popular because it is non intrusive to the circuit being monitored.
There is no direct physical or electrical connection in the circuit. The only link between
the circuit being monitored and the current transformer is the magnetic field which is
developed around the primary conductor as current flows through it. The torroidal type in
general also has the lowest cost associated with it. While a few manufacturers offer
torroidal current transformers of the 2.5 and 5.0 KV voltage class, the vast majority of
torroidal type current transformers are 600V class. It is possible to use a 600V class
torroidal type current transformer in higher voltage class circuits if the primary
conductor is fully insulated and shielded or the current transformer is placed on a
bushing that is designed and rated for the circuit voltage class. Most of the switchgear
circuit breaker manufactures design the bushings so they will accept one or more 600V
class current transformers even though the breaker is rated 15KV class. This approach is
much more cost effective as the cost of a 600V class compared to a 15KV class current
transformer is relatively much less.
RATIO ADJUSTMENT
Another reason for the popularity of the torroidal type of design and construction is
that with relative ease the transformers ratio may be adjusted. You can make course
adjustments by adding primary turns. For example, let's say you need a ratio of 50:5A, but
you only have a 100:5A current transformer available. You can simply take two primary
turns (100/2 = 50) and adjust the 100:5A to a 50:5A current ratio current transformer.
This is accomplished by looping the primary conductor so it passes through the window two
times. This technique is often used to achieve improved accuracy and burden capability at
the lower current ratios. In general, the greater the current ratio the better the
accuracy and burden capability is with current transformers. Therefore, you can take, for
example, a 100:5A current transformer, take four primary turns and make it a 25:5A ratio
(100/4 = 25), and enjoy the better 100:5A performance characteristics at the 25:5A current
ratio. It is possible to make fine adjustments to the current by applying secondary turns
to the current transformer. For example, you may have a 100:5A current ratio current
transformer and need a 90:5A current ratio. Dependent upon how the secondary turns are
applied (additive or subtractive) you can adjust the primary rating by 5 amps for each
secondary turn. To take the 100:5A current ratio and adjust it to 90:5A you only need to
apply two subtractive secondary turns. These course and fine adjustments can be made in
the field only with the torroidal type current transformers.
WOUND PRIMARY CURRENT TRANSFORMERS
The main difference between the torroidal and wound primary type current transformers
is the wound primary type has an internal primary winding and has no window for a primary
conductor to pass through. The wound primary type has an advantage in that the designer
can make the units with low current ratios have better accuracy and burden capabilities.
The wound primary type's primary is actually inserted in series with the conductor which
is to be monitored. This then is intrusive in the circuit to be monitored. For this reason
there is some hesitation to use the wound primary even though it may be the most effective
way to achieve the desired performance, especially for the low current ratio requirements.
The wound primary types may be designed using the torroidal type core because of its
excellent efficiency. In this case a window is not provided as it is not needed. The wound
primary type is more common in the higher (greater than 600V class) voltage class current
transformers as it makes the problems of the higher voltages easier for the design
engineer to cope with while keeping the design as cost effective as possible.
BAR TYPE CURRENT TRANSFORMERS
A true bar type current transformer is a torroidal type transformer with a bus bar as
an integral part of the current transformer which is permanently inserted through the
window of the torroid. The bus bar serves as the primary conductor. The bar type is
inserted in the circuit to be monitored. It is a common error to refer to a wound primary
type as a bar type because the primary connections are made to bus bars. In the wound type
the bus bars are a means of connection and are not a continuous bar.
VARIATIONS
While the torroidal wound primary and bar type are the three major types of current
transformers, there are many possible variations of thee types such units with tapped
windings, multiple windings and multiple cores. Multi ratio current transformers are
common. This is, in fact, a tapped secondary which through reconnection can have numerous
different ratios. ANSI standard C57.13 defines multi ratios as follows:
600:5MR - 50:5, 100:5, 150:5, 200:5, 250:5, 300:5, 400:5, 500:5 and 600:5.
1200:5MR - 100:5, 200:5, 300:5, 400:5, 500:5, 600:5, 800:5, 900:5, 1000:5 and 1200:5.
2000:5MR - 300:5, 400:5, 500:5, 800:5, 1100:5, 1200:5, 1500:5, 1600:5 and 2000:5.
3000:5MR - 300:5, 500:5, 800:5, 1000:5, 1200:5, 1500:5, 2000:5, 2200:5, 500:5 and 3000:5.
4000:5MR - 500:5, 1000:5, 1500:5, 2000:5, 2500:5, 3000:5, 3500:5 and 4000:5.
5000:5MR - 500:5, 1000:5, 1500:5, 2000:5, 2500:5, 3000:5, 3500:5, 4000:5 and 5000:5.
The above is the standard ANSI multi ratios with their respective taps. It is possible
to get other multi ratio ratings with different taps as the need requires.
Another common variation is the split core or take apart current transformer. This
variation is used to install monitoring of a circuit when it is not desirable to open the
circuit to install the torrodial or wound primary type. The split core is commonly
rectangular in shape. It should be noted another variation is a rectangular shaped current
transformer (non-split core or non-take apart).
Another variation is the three phase current transformer which is simply nothing more
than three single phase current transformers in a common case.
The ground fault sensor is a current transformer that is designed to work with a
specific ground fault relay. The ground fault sensor is designed to provide an adequate
current to cause the ground fault relay to be tripped at a predetermined level.
CONSIDERATIONS
The following are considerations which need to be made in order to properly select a
current transformer.
1. "INDOOR OR OUTDOOR" Determine if the transformer is going to be subjected
to the elements or not. Indoor transformers are usually less costly than outdoor
transformers. Obviously, if the current transformer is going to be enclosed in an outdoor
enclosure, it need not be rated for outdoor use. This is a common costly error in
judgement when selecting current transformers.
2. "WHAT DO YOU WANT TO DO" If you want an indication, the first thing you
need to know is what degree of accuracy is required. For example, if you simply want to
know if a motor is lightly or overloaded, a panel meter with a 2 to 3% accuracy will
likely suit your needs. In that case the current transformer need to be only 0.6 to 1.2%
accurate. On the other hand, if you are going to drive a switchboard type instrument with
a 1% accuracy, you will want a current transformer with a 0.3 to 0.6 accuracy. You must
keep in mind that the accuracy ratings are based on rated primary current flowing and per
ANSI standards may be doubled (0.3 becomes 0.6%) when 10% primary current flows. As
mentioned earlier, the rated accuracies are at stated burdens. You must take into
consideration not only the burden of the load (instrument) but you must consider the total
burden. The total burden includes the burden of the current transformers secondary
winding, the burden of the leads connecting the secondary to the load, and of course, the
burden of the load itself. The current transformer must be able to support the total
burden and to provide the accuracy required at that burden.
If you are going to drive a relay you must know what relay accuracy the relay will
require.
3. "VOLTAGE CLASS" You must know what the voltage is in the circuit to be
monitored. This will determine what the voltage class of the current transformer must be
as explained earlier.
4. "PRIMARY CONDUCTOR" If you have selected a current transformer with a
window you must know the number, type and size of the primary conductor(s) in order to
select a window size which will accommodate the primary conductors.
APPLICATIONS
The variety of applications of current transformers seem to be limited only by ones
imagination. As new electronic equipment evolves and plays a greater role in the
generation, control and application of electrical energy, new demands will be placed upon
current transformer manufacturers and designers to provide new products to meet these
needs. |