DATA STREAM Digital, 1-Element
DATA STREAM Digital, 2-Element
DATA STREAM Digital, 3-Element
True RMS AC, 1-Element
True RMS AC, 2-Element
True RMS AC, 3-Element
Avg AC, 1-Element
Avg AC, 2-Element
Avg AC Amps to 0-5 V
Avg AC Amps to 4-20mA, 2 wire
Avg AC Amps to 4-20mA, 4 wire
AC/DC Amps
DC Amps
DATA STREAM Digital, 1-Element
DATA STREAM Digital, 2-Element
DATA STREAM Digital, 3-Element
True RMS AC, 1-Element
True RMS AC, 2-Element
True RMS AC, 3-Element
Avg AC, 1-Element
Avg AC, 2-Element
Avg AC Amps to 0-5 V
Avg AC Amps to 4-20mA, 2 wire
Avg AC Amps to 4-20mA, 4 wire
AC/DC Amps
DC Amps
|
|
|
Understanding Ratio Error
UNDERSTANDING CURRENT TRANSFORMER RATIO ERROR AND EXCITATION CURVES
A current transformer follows all the standard physical laws for electrical
transformers. The primary winding is usually a very low impedance and therefore treated as
a "brute force" constant current source. Faraday's law of ampere-turn balance
states that the number of turns in the primary winding times the primary current must
equal the number of turns in the secondary winding times the secondary current. Therefore,
since the primary is a constant current source, the secondary becomes a constant current
source proportional only to the turns ratio.
Other factors come in to play that affect the basic Faraday's relationship, such as the
non-linear properties of the core material, eddy current, hysteresis and IR losses. As
Figure 1 illustrates, the eddy current and hysteresis losses act to shunt current across
the transformer secondary and are defined as excitation losses IE. Since the excitation
losses are non-linear, they are determined from an Excitation Curve provided by the
transformer's manufacturer. The IR losses act as a resistance RS in series with the
secondary winding.
As Figure 2 illustrates, the secondary voltage Es is found on the vertical axis and the
secondary exciting current IE can be found on the horizontal axis. This exciting current
can best be described as the current that contributes to the current transformation ratio
error.
Power transformers use the terms "Load" and "Regulation" to
describe their operation. Current transformers use the terms "Burden" and
"Accuracy" respectively to describe similar functions. Burden defines the
connection made to the secondary winding to differentiate it from the primary connection
that is generally described as the Load. Current transformers use the term Accuracy to
describe what would generally be considered Regulation with a power transformer. It is
important to remember that Burden and Accuracy are interdependent; generally the lower the
Burden resistance, the better the Accuracy.
Designs that have the current transformer separate from the instrumentation resistor RI
need to consider transformer ratio error. An example would be an ampere meter that uses an
external current transformer. The transformer must have an accurately-defined current
ratio to allow for interchangeability with other transformers of the same rating.
Designs that have the current transformer as an integral part of the instrumentation
can place less emphasis on ratio error and consider more on the transformer's linearity.
An example would be a printed- circuit-board-mounted current transformer that inputs into
an operational amplifier circuit. Ratio error can generally be minimized during
calibration with adjustment to the offset and gain controls. The major concern to the
overall accuracy of the design would then be linearity of the transformer through out the
operating range.
In practice, the designer must consider various factors in selecting a current
transformer: since the secondary is operating as a constant current source, a Burden
resistor of lower value will provide improved accuracy but decrease instrumentation
voltage (V=IR). As the instrumentation voltage is increased with a high Burden resistor,
the power dissipated may become a factor (P = I2 R). Generally the designer determines the
lowest voltage the electronics can handle considering such parameters as circuit noise and
gains. Then the value of the burden resistor can be determined, knowing the
characteristics of the current transformer and overall design requirements.
An example of calculating the actual secondary current, instrumentation voltage and
error percentage is as follows:
- Determine the total burden terminal resistance RB across the secondary of the current transformer.This includes the secondary instrumentation resistance RI and any resistance in the interconnecting leads RL.
For: RI = 0.02 ohm & RL = 0.01 ohm RB =.02 +.01 = .03 ohm
- Add the total burden resistance to the secondary winding DC resistance RS.From figure 2 for a 200:5 current ratio transformer:
RS = 0.034 ohms.03 + 0.034 = .064 ohms
- Select a value of secondary current at a point you desire to determine the ratio error.
For: IS = 3.75 A
- Calculate the secondary voltage ES required for the current to flow through the total secondary resistance.
ES = IS x R ES = 3.75 x 0.064 = .24 V
- Find the secondary voltage ES on the vertical scale of the excitation curve and read over to the 200 line and down to the horizontal scale for the secondary exciting current IE.
IE = .013 A
The primary current will be the turns ratio times the sum of the exciting current and the secondary current
IP = NS / NP x (IE + Is). IP = 40 x (.013 + 3.75) = 150.52 A7.
The voltage developed across the instrumentation resistor will be the secondary current times the instrumentation resistor
EI = IS x RI.EI =3.75 x .02 = 0.075 V
To calculate the percentage ratio error,divide the exciting current by the secondary current times 100.
IE / IS x 100..013 / 3.75 x 100 = 0.35 %
|
CR MAGNETICS, INC.
3500 Scarlet Oak Blvd, St. Louis, MO 63122 USA
Phone: 636.343.8518 Fax: 636.343.5119
Email:sales@crmagnetics.com
|
|
 |
 |
|
| ©2002 CR Magnetics, Inc. |
|
|