Supplied with short circuiting secondary terminal cover
Vacuum cast in polyurethane resin.
Other ratios, secondary currents and dual ratios are avail- able. Refer to factory.
The transformers are tested for partial discharge to Canadian Standards CAN3-C13-M83. This test can also be carried out to IEC requirements if requested.
Specifications
Primary Terminals: 1/2-13 bolts with one Belleville washer.
Secondary Terminals: Brass studs No. 10-32 with one flatwasher, lockwasher and regular nut.
Frequency: 50-400Hz.
Maximum System Voltage: 5.6kV, BIL 60kV full wave.
Continuous Thermal Current Rating Factor 1.50 at 30° C amb., 1.33 at 55° C amb. 150:5 and 600:5 1.33 at 30° C amb., 1.00 at 55° C amb. 250:5 1.00 at 30° C amb., 0.85 at 55° C amb.