Average RMS Current Transducer
CR4410S Split Core Current Transducers
Item #:
CR4410S
Our Price:
$163.52
Input range
0- 5 Amps
0-10 Amps
0-15 Amps
0-20 Amps
0-30 Amps
0-40 Amps
0-50 Amps
0-60 Amps
0-75 Amps
0-100 Amps
0-150 Amps
0-200 Amps
0-400 Amps
0-500 Amps
Power Supply
None Selected
CRPS24VDC-120 - ($82.59)
CRPS24VDC-240 - ($91.48)
Quantity:
The CR4410S Series Average RMS Current Transducers and Transmitters are designed to provide a calibrated DC output proportional to the AC current input. Designed for multi-point current sensing, these devices provide excellent features in a high value package. Average RMS is recommended when sensing current waveforms that have a fixed frequency, and are usually for loads operated from standard utility power.
Specifications / Catalog Page
Application Guides
Developing Voltage From 4-20mA Current Loops
Using External Current Transformers with Other Devices
Step File / Drawing
CR4410-11-20 Split Core Step File
Current
AC Current
Frequency
AC Frequency
Split Core
True
RMS
Average RMS
Elements
Single Element
Outputs
0-5 VDC
Power
24 Vdc Power
Mount
DIN Rail Mount,Panel Mount
More Details
Distributors
Also in Average RMS Current Transducer
Features
Analog 0-5 Vdc output
24 Vdc powered
Use with external current transformers
Highest precision available
Connection diagram printed on case
Specifications
Basic Accuracy: 0.5%
Calibration: Average Sensing, RMS Calibrated
Thermal Drift: 500 PPM/°C
Operating Temperature: 0°C to +60°C
Installation Category: CAT II
Polution Degree: 2
Insulation Voltage: 2500 Vdc
Altitude: 2000 meter max.
Frequency Range: 50 Hz - 400 Hz
MTBF: Greater than 100 K hours
Cleaning: Water-dampened cloth
Supply Voltage: 24 Vdc ±10%
Output Load: 2kΩ or Greater
Response Time: 250 ms max. 0-90% FS
Relative Humidity: 80% for temperatures up to 31°C and decreasing linearly to 50% at 40°C
Applications
Multi-point current sensing and control panels
Monitor Motor Faults
Monitor Heating Elements
Monitor Lighting Elements
Click on Distributor's logo above to view product on their site.