Transducers
C
49
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web:
http://www.crmagnetics.comE-mail:
sales@crmagnetics.comThe Professional
Energy Monitoring
Company
ISO 9001:2008QualityManagementSystem
M N TI
SPECIFICATIONS
DC Voltage Transducer
NOTE: The building installation must have a switch or circuit-breaker that is in close proximity and within easy reach of the operator. The switch or circuit breaker
shall be marked as the disconnecting device for the equipment.
DIN RAIL / PANEL MOUNT, RMS
CR5310
5 VDC Output
CR5311
10 VDC Output
CR5320
4 - 20 mADC Output
INPUT 1
+ -
OUTPUT 1
1
2
3
4
5
6
7
8
9
SUPPLY
+
+
-
-
INPUT 1
OUTPUT 1
1
2
3
4
5
6
7
8
9
SUPPLY
+ -
+
+
-
-
CONNECTION DIAGRAM
Basic Accuracy:....................... 1.0 %
Linearity:................................... 10% to 100% FS
Thermal Drift:........................... 500 PPM/°C
Operating Temperature:........... 0°C to +50°C
Installation Category:............... CAT II
Vibration Tested To:................. IEC 60068-2-6,1995
Pollution Degree:..................... 2
Altitude:................................... 2000 meter max.
Response Time: .................... 250 ms. max.
Insulation Voltage:................... 2500 VDC
Cleaning:................................. Water-dampened cloth
Supply Voltage:............. 24 VDC ±10%
Frequency Range:........ DC only
Output Load:.................. 4-20 mADC - 0 to 300
Ω
0-5 VDC - 2K
Ω
or Greater
Relative Humidity:........ 80% for temperatures up to
31°C and decreasing linearly
to 50% at 40°C
Supply Current:
CR5310:........................ Typical 35mA Max 40mA
CR5320:........................ Typical 35mA Max 40mA
Torque Specs.:.............. 3.0 inch lbs. (0.4Nm)
Weight:.......................... 0.5 lbs.
3.5)
OUTLINE DRAWING
1.16
(29.5)
0.20
(5.1)
(83)
3.268
1.2
(31
(36)
0.14
(3.5)
1.06
(26.8)
2.874
(73)
0.79
(20)
5
6
7
8
9
1
2
3
4
1.42
(36)
Dimensions for All CR5300 Series (shown)