Table of Contents Table of Contents
Previous Page  71 / 162 Next Page
Information
Show Menu
Previous Page 71 / 162 Next Page
Page Background

71

Current Switch - Normally Closed

The

CR9400

Series is a low cost, self powered, fixed set-point Current

Switch designed for applications that require an on-off indication of

current flow.

The normal state of the switch is On when the current level is zero. Cur-

rent levels above the guaranteed full-off level will turn the output to Off.

The Current Switch is recommended only for applications where the

continuous operating level is above the rated full on level of 350 mA.

Operation below this point will not drive the output device full-on and

derate the output ratings.

The unit available with a SCR output for switching AC. Connections can

be made directly to items such as a PLC or electro-mechanical relay.

Note that connections made directly to an inductive device such as an

electro-mechanical relay will require a customer supplied clamping

diode for DC operation or a snubber network for AC operation.

Applications

Continuity

Proving Switch

Features

Low Cost

Low Fixed Trip Point

Fully Isolated

Self-Powered

Specifications

Rated Full-off: 0.400 AAC RMS

Turn-on Time: 100 ms. max. @ rated full-on

Turn-off Time: 250 ms. max. to 80% of Vce

Maximum sense current: Continuous: 100 AAC

1 Second: 500 AAC

Frequency*: 50 to 400 Hz

Operating Temperature: -30° C to +60° C

Storage Temperature: -55° C to +85° C

Weight 0.08 LBS.

*All specifications for operation at 60 Hz only

Regulatory Agencies

CR9400 Series

PART NUMBER

CR

-

-

CURRENT SWITCH

Relays, Switches, & Sensors

3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119

Web:

http://www.crmagnetics.com

E-mail:

sales@crmagnetics.com

The Professional

Energy Monitoring

Company

ISO9001:2008QualityManagementSystem

M N TI

DC SWITCHING (-NPN or -PNP)

Vce (full off): 30 VDC max.

Isink (full on): 120 mADC max.@ rated full-on

Vce (reverse polarity voltage): 1.2 VDC @

100 mADC

Vce (full on): 1.5 VDC @ 120 mADC Isink

Off state leakage current: 5ua @ 30 VDC

(typical)

AC SWITCHING (-ACA)

Off state voltage: 240 VAC RMS max.

Minimum holding current: 10 mA

On state current: 0.8 AAC RMS max. continuous

Off state leakage: 50 ua @ 240 VAC max.

Peak Non-Repetitive Surge Current:

8 AAC RMS (1 cycle, 60 Hz.)

ELECTRICAL CONNECTIONS

9421

.27 dia. Window

9450

61dia.Window

9480

0.40 dia. Window

NPN

Transistor Output

PNP

Transistor Output

ACA

AC Output

M

Mounting Case

(Optional)

ORANGE+

BLACK -

Vce

I source

V+

RED+

BLACK -

V+

I sink

Vce

BLACK

VAC

BLACK

-NPN

-PNP

-ACA

D

E234389

CR9421 Non-Mounting Base

CR9450 Non-Mounting Base

CR9480 Non-Mounting Base

CR9480 with Mounting Base