Current Transformers

F

3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119

Web:

http://www.crmagnetics.com

E-mail:

sales@crmagnetics.com

The Professional

Energy Monitoring

Company

ISO 9001:2008QualityManagementSystem

M N TI

Medium Voltage Current Transformer

CTW5-L-110 & CTWH5-L-110

Applications

Metering and relaying.

Frequency

50 - 400 Hz.

Maximum System Voltage

15.5kV, BIL 110kV full wave.

Continuous Thermal Current Rating

Factor

1.00 at 30° C amb., 0.85 at 55° C amb.

Primary Terminals

1/2-13 bolts with one Belleville washer.

Secondary Terminals

Brass screws No. 10-32 with one flatwasher & lockwasher.

Vacuum cast in polyurethane resin.

Other ratios, secondary currents and dual ratios are avail-

able. Refer to factory.

The transformers are tested for partial discharge to Canadian

Standards CAN3-C13-M83. This test can also be carried out to

IEC requirements if requested.

Approximate weight

34 lbs.

Regulatory Agencies

Part Number*

Current

Ratio

Relay

Class

B0.1 B0.2 B0.5 B0.9 B1.8

ANSI Metering Class at 60 Hz

Thermal Current Rating

1 second RMS Amps

CTW5-L-110-T20-050

5:5

T20 0.3 0.3 0.6 1.2 2.4

375

CTW5-L-110-T20-100

10:5

T20 0.3 0.3 0.6 1.2 2.4

590

CTW5-L-110-T20-150

15:5

T20 0.3 0.3 0.6 1.2 2.4

1200

CTW5-L-110-T20-250

25:5

T20 0.3 0.3 0.6 1.2 2.4

1700

CTW5-L-110-T20-300

30:5

T20 0.3 0.3 0.6 1.2 2.4

1700

CTW5-L-110-T20-400

40:5

T20 0.3 0.3 0.6 1.2 2.4

2400

CTW5-L-110-T20-500

50:5

T20 0.3 0.3 0.6 1.2 2.4

4715

CTW5-L-110-T25-750

75:5

T25 0.3 0.3 0.6 1.2 2.4

4715

CTW5-L-110-T25-101

100:5

T25 0.3 0.3 0.6 1.2 2.4

8625

CTW5-L-110-T25-151

150:5

T25 0.3 0.3 0.6 1.2 2.4

11500

CTW5-L-110-T30-201

200:5

T30 0.3 0.3 0.6 1.2 2.4

11500

CTW5-L-110-T20-251

250:5

T20 0.3 0.3 0.6 1.2 2.4

21700

CTW5-L-110-T25-301

300:5

T25 0.3 0.3 0.6 1.2 2.4

21700

CTW5-L-110-T30-401

400:5

T30 0.3 0.3 0.6 1.2 2.4

44700

CTW5-L-110-T35-501

500:5

T35 0.3 0.3 0.3 0.6 1.2

44700

CTW5-L-110-T40-601

600:5

T40 0.3 0.3 0.3 0.6 1.2

44700

CAUTION: Use only the Belleville washers supplied. Tighten to between 25 and 30 foot-pounds. Do not overtighten.

* For ordering with primary bars, change model number to CTWH5-L. A test card is provided with each unit.

BAR SIZES

PRIMARY CURRENT

DIMENSIONS

A B

5 TO 250A

0.25 1.50

300 TO 1200A