Table of Contents Table of Contents
Previous Page  123 / 162 Next Page
Information
Show Menu
Previous Page 123 / 162 Next Page
Page Background

123

Potential Transformers

G

Application Notes

3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119

Web:

http://www.crmagnetics.com

E-mail:

sales@crmagnetics.com

The Professional

Energy Monitoring

Company

ISO 9001:2008QualityManagementSystem

M N TI

1. Delta Connected Supply Systems

When applying voltage transformers to ungrounded delta connected supply systems, the transformer must not be connected in wye with the wye-point con-

nected to neutral ground, or ungrounded. The advent of zero sequence currents caused by a ground fault in the system will cause damage, and eventual

destruction of the transformer if the fault is not quickly removed.

2. Ferro resonance

Most voltage transformers are lightly loaded, particularly when associated with watthour metering and relaying schemes. If the voltage transformer has one

primary lead grounded, and during an abnormal condition creating a large overvoltage, the transformer may saturate, and its impedance may cause a res-

onance with the system capacitance. This resonance, or oscillation, may be sustained and could destroy the voltage transformer. If, however, the secondaries

are connected in delta, with a broken arrow, and a suitable resistor is connected across the broken corner, then ferro resonance can be damped. Our recom-

mendation for the resistive value is shown on the catalog sheet where it applies. The power rating is determined by the user.

3. Secondary Circuit Check

Immediately prior to connecting the burden and leads to the transformer, a check of the impedance at that circuit should be made. This will avoid a possible

short-circuit connection to the transformer, if a short-circuit is applied to the transformer, it can be withstood for one second. Note: Only secondary circuit

fuses can adequately protect the transformer from such a short circuit.

4. Primary Fuse Rating

Values shown are suggested for normal installations, in order to protect the system from a voltage transformer failure. Higher ratings at users option, may

be used to avoid unusual clearing due to conditions resulting from magnetizing in-rush.

ROUTINE FACTORY TESTS

VOLTAGE

CLASS

NO. OF BUSHINGS

CONNECTION

LV 1 MIN

60Hz

H2 1 MIN

60Hz

HV 1 MIN

60Hz

INDUCED

18 SEC. 400Hz

5kV

1

L - GND N

2.5kV

10 kV

NA

15kV OR 19kV

2

L - L

2.5kV

NA

15kV OR 19kV

DOUBLE VOLTAGE

8.7kV

1

L - GND N

2.5kV

10 kV

NA

26kV

2

L - L

2.5kV

NA

26kV

DOUBLE VOLTAGE

15kV

1

L - GND N

2.5kV

10 kV

NA

34 kV

2

L - L

2.5kV

NA

34kV OR 36kV

DOUBLE VOLTAGE

25kV

1

L - GND N

2.5kV

10 kV

NA

kV

2

L - L

2.5kV

NA

kV

DOUBLE VOLTAGE

34.5kV

1

L - GND N

2.5kV

10 kV

NA

70 kV

2

L - L

2.5kV

NA

70kV OR 80kV

DOUBLE VOLTAGE

Routine Factory Tests include: Polarity, accuracy, and partial discharge per CANADIAN STANDARDS (CAN3-C13-M83) (Partial discharge can also be carried out to IEC

requirements on request)

ANSI BURDEN DATA

CONNECTION

VA

POWER FACTOR

ANGLE

W

12.5

0.10

84.3

°

X

25

0.70

45.6

°

M

35

0.20

78.5

°

Y

75

0.85

31.8

°

Z

200

0.85

31.8

°

ZZ

400

0.85

31.8

°