Table of Contents Table of Contents
Previous Page  129 / 162 Next Page
Information
Show Menu
Previous Page 129 / 162 Next Page
Page Background

129

Potential Transformers

G

PTW3-1-60

The PTW3-1-60 Series

of potential transformers are designed to give accurate

measurement of medium voltage systems up to 5KV by stepping down higher voltages

to 120 VAC. Useful for monitoring and measuring larger power systems and distribu-

tion networks containing medium voltage loads. These devices have increased capa-

bility to drive larger VA loads.

TWO BUSHING (a)

CATALOG NUMBERS

GROUP

PRIMARY

VOLTAGE

RATIO

SECONDARY

VOLTAGE

UNFUSED

FUSES

FUSE CLIPS ONLY (d)

SWITCHGEAR STYLE

1

*2400

20:1

120

PTW3-2-60-242

PTW3-2-60-242FF PTW3-2-60-242CCSorCCL PTW3-2-60-242SS

2

3300

30:1

110-50Hz

PTW3-2-60-332

PTW3-2-60-332FF PTW3-2-60-332CCSorCCL PTW3-2-60-332SS

2

4200

35:1

120

PTW3-2-60-422

PTW3-2-60-422FF PTW3-2-60-422CCSorCCL PTW3-2-60-422SS

2

*4800

40:1

120

PTW3-2-60-482

PTW3-2-60-482FF PTW3-2-60-482CCSorCCL PTW3-2-60-482SS

One Bushing (b)

CATALOG NUMBERS

GROUP

PRIMARY

VOLTAGE

RATIO

SECONDARY

VOLTAGE

R FR

(c)

FUSES

FUSE CLIPS ONLY (d)

SWITCHGEAR STYLE

4A

*2400

20:1

120

230

PTW3-1-60-242F

PTW3-1-60-242CSorCL

PTW3-1-60-242S

4B

*4200

35:1

120

230

PTW3-1-60-422F

PTW3-1-60-422CSorCL

PTW3-1-60-422S

4B

*4800

40:1

120

230

PTW3-1-60-482F

PTW3-1-60-482CSorCL

PTW3-1-60-482S

PART NUMBERS

UNFUSED

TWO BUSHING

ONE FUSE

ONE BUSHING

TWO FUSE

TWO BUSHING

H1

X2

X2

X1

X2

X1

X1

H1

H1

H2

H2

H2

3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119

Web:

http://www.crmagnetics.com

E-mail:

sales@crmagnetics.com

The Professional

Energy Monitoring

Company

ISO 9001:2008QualityManagementSystem

M N TI

E145172

LR89403

Manufactured to meet the

requirements of ANSI/IEEE C57.13

Frequency

60 Hz.

Maximum System Voltage:

5.6kv, BIL 60kV.

Use with CR Magnetics Transducers

Accuracy Class:

0.3 WXMY, 1.2 Z at 100% rated voltage with 120V based

ANSI Burden

0.6 WX, 1.2 MY at 58% rated voltage with 69.3V based

on ANSI burden

Thermal Rating:

750 VA at 30° C . amb., 500 VA at 55°C. amb

Approximate weight 34 lbs., unfused

Regulatory Agency

: