Potential Transformers

G

3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119

Web:

http://www.crmagnetics.com

E-mail:

sales@crmagnetics.com

The Professional

Energy Monitoring

Company

ISO 9001:2008QualityManagementSystem

M N TI

468 Potential Transformers

The 468 Series

of potential transformers are designed to give

accurate measurement of low voltage systems (up to 600 VAC) by

stepping down higher voltages to 110 VAC. Useful for monitoring

and measuring incoming building or factory voltages.

468

PART NUMBERS

Part Number

Voltage Rating

Turns Ratio

Rec. Primary

Fuse Rating

468-069

69.3:120

0.58:1

3.0

468-120

120:120

1:1

2.0

468-208

208:120

1.73:1

1.0

468-240

240:120

2:1

1.0

468-277

277:120

2.31:1

1.0

468-288

288:120

2.4:1

0.75

468-300

300:120

2.5:1

0.75

468-346

346:120

2.88:1

0.75

*

468-480

*

480:120

4:1

0.50

*

468-600

*

600:120

5:1

0.40

19.05

.75

33.27

1.31

55.63

2.19

71.37

2.81

LABEL

H1

H2

X1

X2

35.05

1.38

76.20

3.00

92.20

3.63

(4) HOLES

5.59

.22

DIA.

28.58

1.13

93.47

3.68

103.12

4.06

9.65

.38

(2) BOSSES

3/8 DIA.

E93779

LR89403

Manufactured to meet the

requirements of ANSI/IEEE C57.13

Frequency

60 Hz.

*Models designed specifically for 50 hz operations are

available with reduced performance. Contact factory for

details

Standard Secondary Voltage:

120 Volts

Use with CR Magnetics Transducers

Insulation Level:

600 Volt, 10 kV BIL full wave

Accuracy Class:

+/- 0.6% at all burdens up to 7.5 VA at 1.0 and +/- 1.5%

20 VA burden

Thermal Rating:

75 VA at 30° C . amb., 50 VA at 55°C. amb

Terminals are No. 10-32 screws with one lockwasher and

one flatwasher.

Approximate weight 4 lbs.

Regulatory Agencies

: