127

Potential Transformers

G

PT3-1-45 and PT3-2-45

The PT3-1-45 and PT3-2-45 Series

of potential transformers are designed to

give accurate measurement of medium voltage systems up to 5KV by stepping down

higher voltages to 120 VAC. Useful for monitoring and measuring larger power sys-

tems and distribution networks containing medium voltage loads.

TWO BUSHING (a)

CATALOG NUMBERS

GROUP

PRIMARY

VOLTAGE

RATIO

SECONDARY

VOLTAGE

UNFUSED

FUSES

FUSE CLIPS ONLY (d) SWITCHGEAR STYLE

1

840

7:1

120

PT3-2-45-841

PT3-2-45-841FF

PT3-2-45-841CC

PT3-2-45-841SS

1

1200

10:1

120

PT3-2-45-122

PT3-2-45-122FF

PT3-2-45-122CC

PT3-2-45-122SS

1

2400

20:1

120

PT3-2-45-242

PT3-2-45-242FF

PT3-2-45-242CC

PT3-2-45-242SS

2

3300

30:1

110-50Hz

PT3-2-45-332

PT3-2-45-332FF -----PT3-2-45-332CC PT3-2-45-332SS

2

4200

35:1

120

PT3-2-45-422

PT3-2-45-422FF

PT3-2-45-422CC

PT3-2-45-422SS

2

4800

40:1

120

PT3-2-45-482

PT3-2-45-482FF

PT3-2-45-482CC

PT3-2-45-482SS

One Bushing (b)

CATALOG NUMBERS

GROUP

PRIMARY

VOLTAGE

RATIO

SECONDARY

VOLTAGE

R FR

(c)

FUSES

FUSE CLIPS ONLY (d) SWITCHGEAR STYLE

4A

2400

20:1

120

190

PT3-1-45-242F

PT3-1-45-242C

PT3-1-45-242S

4B

4200

35:1

120

190

PT3-1-45-422F

PT3-1-45-422C

PT3-1-45-422S

AB

4800

40:1

120

190

PT3-1-45-482F

PT3-1-45-482C

PT3-1-45-482S

PART NUMBERS

UNFUSED

TWO BUSHING

ONE FUSE

ONE BUSHING

TWO FUSE

TWO BUSHING

H1

X2

X2

X1

X2

X1

X1

H1

H1

H2

H2

H2

3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119

Web:

http://www.crmagnetics.com

E-mail:

sales@crmagnetics.com

The Professional

Energy Monitoring

Company

ISO 9001:2008QualityManagementSystem

M N TI

E145172

LR89403

Manufactured to meet the

requirements of ANSI/IEEE C57.13

Frequency

60 Hz.

Maximum System Voltage:

5.6kV, BIL 45kV.

Use with CR Magnetics Transducers

Accuracy Class:

0.3 WX, 0.6 MY,1,2Z at 100% rated voltage with 120V

based ANSI Burden

0.6 WX, 1.2 MY at 58% rated voltage with 69.3V based

on ANSI burden

Thermal Rating:

600 VA at 30° C . amb., 400 VA at 55°C. amb

Switch gear style is similar to fused style. No fuse or Fuse

clip is provided, but inserts for fuse clips are supplied.

Approximate weight 20 lbs., unfused

Regulatory Agencies

: