Current Transformers

F

3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119

Web:

http://www.crmagnetics.com

E-mail:

sales@crmagnetics.com

The Professional

Energy Monitoring

Company

ISO 9001:2008QualityManagementSystem

M N TI

Typical Applications

The actual current ratio may be changed from the name-

plate ratio by wrapping the primary and/or secondary

leads through the window opening.

ACTUAL

TURNS

RATIO

NAMEPLATE RATIO

NUMBER OF SECONDARY TURNS

THROUGH WINDOW OPENING

NUMBER OF PRIMARY TURNS

THROUGH WINDOW OPENING

=

±

125

5

3

11

2

=

TURNS RATIO = 11:1

CURRENT RATIO = 55:5

This illustration shows how a current transformer with a

nameplate turns ratio of 125:5 can be rescaled to oper-

ate as a non-standard 55:5 ratio transformer.

WHERE:

Nameplate ratio = 125 (125/5)

Number of secondary turns through window = - 3

Use -3 because the secondary wire is routed from X1 terminal

first

through the H1 side and out the H2 side

(Use + if the wire was routed first through the X2 side)

Number of primary turns through window = 2

-

Wire from X1 terminal is routed through

the H1 side and out the H2 side

+

Wire from X1 terminal is routed through

the H2 and out the H1 side

PRIMARY

(55 AAC)

SECONDARY

(5 AAC)

Changing Current Transformer Ratios

Example