E-mail:

sales@crmagnetics.com

The Professional

Energy Monitoring

Company

ISO 9001:2008QualityManagementSystem

M N TI

66

Relays, Switches & Sensors

D

Ground Fault Sensor

CR7310 Series

The

CR7310

Series, Ground Fault Sensor provides a reliable

and cost effective method for sensing ground faults. The cur-

rent-carrying wires are routed through the opening extending

from the top of the case. When ground current reaches the

level set by the trip point adjustment, the relay trips, illuminates

the tripped LED and provides an output signal. A precision

voltage reference circuit ensures a highly repeatable trip point.

The Sensor is rated as a Class 1 device.

OUTPUT OPTIONS

The Relay is available with three different ouput

configurations, electromechanical relay, op-

toisolated NPN transistor or zero-crossing op-

toisolated triac. Specify desired selection in part

number.

DC SWITCHING (-NPN)

Vce (full off): 30 VDC max.

Isink (full on): 120 mADC max.@ rated full-on

Vce (full on): 1.5 VDC @ 120 mADC Isink

Off state leakage current: 5ua @ 30 VDC

(typical)

Terminals: 2

1/4”

Male Q C

RELAY (-ELR)

Arrangement: 1 Form C (SPDT)

Contact Material: Silver-cadmium oxide

Terminals: 3

1/4”

Male QC

Mechanical Life: 10 million operations,

typ.@ rated load

Electrical Life: 100,000 operations,

typ. @ rated load

Initial Contact Resistance:

50 milliohms max. @ 500 mA, 12 VDC

Contact Rating: UL508/873 & CSA

AC SWITCHING (-TRC)

Off state voltage: 240 VAC RMS max.

Minimum switch voltage: 24 VAC RMS

On state current: 500 mA RMS max. continuous

Switching mode: Zero crossing

Off state leakage: 60 ua @ 240 VAC max.

Terminals: 2 @ 1/4” Male QC

E211244

VOLTAGE

LOAD TYPE

240 VAC

240 VAC

N.O. CONTACT

N.C. CONTACT

Resistive

Motor

20A

2HP

10A

1/2 HP

125 VAC

28 VDC

Motor

Resistive

1HP

20A

1/4 HP

10A

Applications

Monitor Electrical Heater Elements

Sense Motor Over/Under Loads

Detect Lamp burn-out

Indicate Phase Loss

Features

Variable Trip Point and Time Delay

Monitors Currents from 10mAAC to 100 AAC Amps

Electrical Isolation Between Circuits

Output Relay Rated up to 20 Amps

LED Trip Status Indicator

Dead Band Prevents Relay Chatter

Calibrated Dial Option Available

External Current Transformers Available

Specifications

Mounting:

3/16” dia. clearance holes on 1

15/16

” by 2

15/16

”centers

Environmental:

Operating Temperature: -30° C to +60° C

Storage Temperature: -55° C to +85° C

Power-On Delay: 100 MS MAX

Hysteresis: 5% Max.

Input Supply Power:

Typical 80mA

Max 100mA

Sensed Current:

Max. Continuous: 200% Full Scale

Frequency: 60-400 Hz *

*All specifications for operation at 60 Hz only

Altitude: 2000 meters max.

(Contact factory for High Altitude applications)

Weight 0.5 LBS.

Regulatory Agencies