Table of Contents Table of Contents
Previous Page  62 / 162 Next Page
Information
Show Menu
Previous Page 62 / 162 Next Page
Page Background

E234389

62

Relays, Switches, & Sensors

D

3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119

Web:

http://www.crmagnetics.com

E-mail:

sales@crmagnetics.com

The Professional

Energy Monitoring

Company

ISO 9001:2008QualityManagementSystem

M N TI

Current Sensing Relay

VOLTAGE

LOAD TYPE

240 VAC

240 VAC

N.O. CONTACT

N.C. CONTACT

Resistive

Motor

20A

2HP

10A

1/2 HP

125 VAC

28 VDC

Motor

Resistive

1HP

20A

1/4 HP

10A

The

CR4395

Series, Current Sensing Relay provides an effec-

tive and highly stable method for monitoring electrical current.

The current-carrying wire is routed through the opening extend-

ing from the top of the case. When current reaches the level set

by the trip point adjustment, the relay trips and starts the ad-

justable timer. After the timer cycles the electromechanical relay

is energized. A precision voltage reference circuit ensures a

highly repeatable trip point.

Applications

Monitor Electrical Heater Elements

Sense Motor Over/Under Loads

Detect Lamp burn-out

Indicate Phase Loss

Features

Variable Trip Point and Time Delay

Monitors Currents from 1 AC to 100 AC Amps

Electrical Isolation Between Circuits

Output Relay Rated up to 20 Amps

LED Trip Status Indicator

Dead Band Prevents Relay Chatter

Calibrated Dial Option Available

External Current Transformers Available

Specifications

Mounting:

3/16” dia. clearance holes on 1

15/16

” by 2

15/16

”centers

Environmental:

Operating Temperature: -30° C to +60° C

Storage Temperature: -55° C to +85° C

Power-On Delay: 100 MS MAX

Hysteresis: 5% Max.

Input Supply Power:

Typical 80mA

Max 100mA

Sensed Current:

Max. Continuous: 200% Full Scale

Frequency: 60-400 Hz *

*All specifications for operation at 60 Hz only

Altitude: 2000 meters max.

(Contact factory for High Altitude applications)

Weight 0.5 LBS.

Regulatory Agencies

OUTPUT OPTIONS

The Relay is available with three different output

configurations, electromechanical relay, op-

toisolated NPN transistor or optoisolated triac.

Specify desired selection in part number.

DC SWITCHING (-NPN)

Vce (full off): 30 VDC max.

Isink (full on): 120 mADC max.@ rated full-on

Vce (full on): 1.5 VDC @ 120 mADC Isink

Off state leakage current: 5ua @ 30 VDC

(typical)

RELAY (-ELR)

Arrangement: 1 Form C (SPDT)

Contact Material: Silver-cadmium oxide

Terminals: 3

1/4”

Male QC

Mechanical Life: 10 million operations,

typ.@ rated load

Electrical Life: 100,000 operations,

typ. @ rated load

Initial Contact Resistance:

50 milliohms max. @ 500 mA, 12 VDC

Contact Rating: UL508/873 & CSA

AC SWITCHING (-TRC)

Off state voltage: 240 VAC RMS max.

Minimum switch voltage: 24 VAC RMS

On state current: 0.5 AAC RMS max. continuous

Switching mode: Zero crossing

Off state leakage: 60 ua @ 240 VAC max.

Terminals: 2 @ 1/4” Male QC

CR4395 Series